>Product>Electrical Test Equipment>Electrical Calibrator>Smart Three Phase Transducer Calibrator

transducer calibrator
transducer calibrator

GF302BSMART THREE PHASE TRANSDUCER CALIBRATOR

GF302B portable smart three phase transducer calibrator is suitable for power plant and power grid companies for the following function: measuring and testing department and instrumentation classes, national levels measuring and testing institutions, railway, petroleum, chemical industry and other large industrial and mining enterprises, scientific research units, etc. The core technology function with 32bit digital signal processor (DSP+MCU) and 24 high-speed digital A/D converters composed of high precision work frequency communication terminal. It can test the basic error of power transducer, the change caused by the influence of voltage, current, waveform, power factor, etc., and the ripple content and response time in the output DC voltage (current) of the transducer. Also as standard three phase ac voltage source and current source, or as DC power source. It is one ideal high precision calibrator in electrical laboratory.

APPLICATION

■ Power plant; ■ Universities; ■ Research institutes; ■ Transducer manufacturers; ■ Electrical testing center; ■ Power meter manufacturers; ■ Panel meter manufacturers; ■ Pointer meter manufacturers; ■ Digital meter manufacturers; ■ Railway electrical department; ■ ISO17025 Electrical laboratory; ■ Power engineering commissioning company; ■ Electricity power bureau & power company; ■ Electrical Department of industrial and mining enterprises;

FUNCTIONS & FEATURES

■ Adopt 32-bit MCU+DSP processor, powerful and flexible;

■ 8.4 inch big screen color display and English interface;

■ With USB & RS232 port, it can connect computer for data management or controlled by PC;

■ For the software calibration, you don't need to open the case, it's stable and reliable;

■ Wide temperature core devices are used to ensure the long-term accuracy of the equipment;

■ With automatic failure detection function, shows fault part, the convenience users check line;

■ Voltage output terminal with short circuit, current output terminal open protection and power amplifier overheating protection function;

■ As one voltage source, current source and power source with high precision and high stability standard resource;

■ The built-in electric measurement transducer, electric measurement instrument and meter instructions of verification program, fully automatic or semi-automatic for verification, and save 10000 group test data;

■ Check all kinds of electric measurement indicating meter, including AC/DC voltmeter, AC/DC ammeter, frequency meter, phase angle meter, single & three-phase ac active power meter, three-phase ac reactive power meter & synchronous meter etc;

■ All kinds of electric measurement transducer can be tested, including AC/DC voltage transducer, AC/DC current transducer, frequency transducer, power factor transducer, single/ three-phase AC active power transducer, three-phase reactive power transducers;

PARAMETERS

Electrical parameters
Accuracy class 0.05%
Power supply Single phase AC 220V±10% or 110V±10%, 50/60Hz
AC Voltage output
Range(U1,U2,U3) 140V, 280V, 600V
Adjusting range (0-120)% RG
Adjust fineness 0.01% RG, 0.1% RG, 1% RG, 10% RG
Accuracy 0.05% RG
Stability 0.01% / 1 min
Distortion ≤0.2% (non-capacitive load)
Load capacity 25VA
Output distortion degree ≤0.2% or (linear load)
AC Current output
Range(I1,I2,I3) 0.2A, 1A, 10A, 20A
Adjusting range (0-120)% RG
Adjust fineness 0.01% RG, 0.1% RG, 1% RG, 10% RG
Accuracy 0.05% RG
Stability 0.01%/1 min
Distortion ≤0.2% (non-capacitive load)
Load capacity 25VA
Output distortion degree ≤0.2% or (linear load)
AC Power output
Accuracy 0.05% RG
Stability 0.01%/1min
Frequency
Frequency range 40.000 - 70.000 Hz
Resolution 0.001 Hz
Accuracy 0.005 Hz
Power factor output
Adjusting range -1 ~ 0 ~ 1
Adjust fineness >0.0001
Accuracy >0.0005
Phase angle
Scope 0°-359.99°
Resolution 0.01°
Accuracy 0.05°
Voltage/Current harmonic output
Times 2-31st
Content 0-40%
Phase 0-359.999 degree
Configuration error (10% RD + 0.1%), RD refers to the configuration value of harmonic contents
DC Voltage output
Range 5V, 65V, 500V, 1000V
Adjusting range (0-120)% RG
Adjust fineness 0.01% RG, 0.1% RG, 1% RG, 10% RG
Accuracy 0.05% RG
Stability 0.01%/1min
Load capacity 25VA
Ripple content ≤1%
DC Current output
Range 0.1A, 0.2A, 1A, 10A, 20A
Adjusting range (0-120)% RG
Adjust fineness 0.01% RG, 0.1% RG, 1% RG, 10% RG
Accuracy 0.05% RG
Stability 0.01%/1min
Load capacity 25VA
Ripple content ≤1%
DC measurements
DC voltage measurement range 0 to ±10V
DC current measurement range 0 to ±24mA
Measurement accuracy 0.01% RG
Functions
LCD display 8.4inch touch TFT color LCD
Data recorder 16G, 10000sets
Programmable by RS232
Communication port USB, RS232, 10/100M LAN
Auto test software Yes
Standard
Standard JJG126-1995, JJG_597-2017, Q/GDW 1899-2013, DL/T1119-2009, DL/T630-1997, JJG124-2005; JJF1587-2016; IEC61010, IEC 61000, IEC 61326
Safety
Isolation protection IEC 61010-1:2001
Measurement Category 300 V CAT III, 600 V CAT II
Degree of protection IP20
Declaration of conformity CE, CNAS certified
Mechanical parameters
Dimensions (W×D×H) (mm) 460x430x185
Weight (kg) 25
Environmental conditions
Working temperature 0°C to 40°C
Storage conditions -30°C to 60°C
Relative humidity ≤85%
(1) RG means range, the same as below;
(2) RD means the setted harmonic content, harmonic can be a single output, also multiple output.