>Product>CT & PT>Instrument Voltage Transformer>12kv High Performance Dry Type Indoor Voltage Transformer

dry type voltage transformer 12KV
dry type voltage transformer 12KV

GFJDZX0966-10G12KV HIGH PERFORMANCE DRY TYPE INDOOR VOLTAGE TRANSFORMER

GFJDZX0966-10G 12KV High Accuracy indoor Voltage transformers are designed for metering and relaying applications. This product has the characteristics of high precision and large capacity, and can be customized according to customer requirements.
The primary and secondary coils are wound using special winding and shielding techniques for improved voltage stress distribution.Each coil is carefully insulated with mylar film to provide a high dielectric medium between layers. The completed winding structure and double-loop cores are assembled to a support frame.

DESCRIPTIONFor insulation and protection, the assembly is cast in hydrophobic cycloaliphatic epoxy (HCEP) using automatic vacuum pressure. The HCEP material offers superior arc track, ozone, and ultraviolet-resistive properties while maintaining physical strength. The hydrophobic surface properties of HCEP ensure highly reliable performance in wet, humid, or polluted environments.
It can be used for medial voltage AIS, or can be used for medial voltage switchgears. They can operate in all kinds of environments (such as wide range temperature (-50~70℃), high altitude, high humidity, high pollution or salt). Strictly Comply IEC60044-2; IEC 61869-1,3; ANSI/IEEE C57.13.

APPLICATION

■ Rail way;

■ Coal Mine;

■ Power Plant;

■ Power Meter;

■ Energy meter;

■ Power station;

■ MV switchgears;

■ Oil, gas company;

■ Distribution boxes;

■ Distribution system;

■ Air insulation cabinet;

■ Measuring instrument;

■ Ring network cabinet;

■ Electric Power Bureau;

■ MV Power Quality Analyzer;

■ Industrial and mining enterprises;

FEATURES

■ Weight: 28KG;

■ Using Life: 30 years;

■ Material:Epoxy (HCEP);

■ Rated voltages up to 12 kV;

■ 12KV 11KV 10KV 6KV indoor;

■ Accuracy class: 0.2 0.5 1 3P 6P;

■ Seconday voltage: (KV) 0.1√3, 0.1

■ Limiting Therminal Output(VA): 400VA;

■ Reasonable structure and robust construction;

■ Rated basic insulation levels (BIL) up to 75 kV;

■ Excellent short circuit and thermal withstand capabilities;

■ Rated voltage primary (KV): 11/√3, 11, 10/√3, 10, 6/√3, 6;

■ IEC60044-2, IEC 61869-1,3 & ANSI/IEEE C57.13 Standards;

PARAMETERS

Technical parameters
Standards IEC60044; IEC 61869; ANSI/IEEE C57.13
Rated Voltage 12KV, 11KV, 10KV, 6KV
Rated load ≤100VA
Secondary voltage output 100V, 110V, 120V, 220V, 380V
Limiting Therminal output 800VA
Rated frequency 50Hz or 60Hz
Cosø 0.8 (lag)
Phase number Single
Class 0.2, 0.5, 1, 3, 3P, 6P
Rated insulation level 12/42/75KV, 7.2/32/60KV
Using type Indoor
Application Measurement and Protection
Insulation class E
Class of pollution II
Mechanical parameters
Material Epoxy resin
Weight (kg) 28
Operating conditions
Operating temperature -25°C to +55°C
Daily average temp <+40°C
Storage temperature -40°C to +70°C
Altitude <1000 meters
Condition No existence of severely begrimed, erosive and radioactive gas in the air. Permission of long-term operation under rated current.

TECHNICAL DATA

Model Rated Voltage Ratio(KV) Class Accuracy class and Rated output(VA) Limiting Therminal Output(VA)
0.2 0.5 1.0 6P
GFJDZX0966-11G 11/√3/0.11/√3/0.11/3 0.2/6P
0.5/6P
1.0/6P
20 60 90 100 800
GFJDZX0966-10G 10/√3/0.1/√3/0.1/3
GFJDZX0966-6G 6√3/0.1/√3/0.1/3
GFJDZX0966-10G 10/√3/0.1/√3/0.1/√3/0.1/3 0.2/0.5/6P 10 15 30 50
GFJDZX0966-6G 6/√3/0.1/√3/0.1/√3/0.1/3