>Product>CT & PT>Instrument Voltage Transformer>20kv Double & Single Pole Outdoor Single Phase Voltage Transformer

double pole single pole voltage transformer
double pole single pole voltage transformer

GFJDZW-20 GFJDZXW-20G20KV DOUBLE & SINGLE POLE OUTDOOR SINGLE PHASE VOLTAGE TRANSFORMER

JDZW-20 and JDZXW-20G 20KV High Accuracy Outdoor Voltage transformers are designed for outdoor metering and relaying applications. This product has the characteristics of high precision and large capacity, and can be customized according to customer requirements.
The primary and secondary coils are wound using special winding and shielding techniques for improved voltage stress distribution.Each coil is carefully insulated with mylar film to provide a high dielectric medium between layers. The completed winding structure and double-loop cores are assembled to a support frame.

DESCRIPTIONFor insulation and protection, the assembly is cast in hydrophobiccycloaliphatic epoxy (HCEP) using automatic vacuum pressure. The HCEP material offers superior arc track, ozone, and ultraviolet-resistive properties while maintaining physical strength. The hydrophobic surface properties of HCEP ensure highly reliable performance in wet, humid, or polluted environments.
It can be used for medial voltage AIS, or can be used for medial voltage switchgears. They can operate in all kinds of environments (such as wide range temperature (-50~70℃), high altitude, high humidity, high pollution or salt). This model JDZW-20 JDZXW-20G outdoor voltage transformer is also as voltage source to supply 220V voltage. Strictly Comply IEC60044-2; IEC 61869-1,3; ANSI/IEEE C57.13.

APPLICATION

■ Rail way;

■ Coal Mine;

■ Power plant;

■ Power Meter;

■ Energy meter;

■ Power station;

■ Oil, gas company;

■ Distribution system;

■ Measuring instrument;

■ Electric Power Bureau;

■ MV Power Quality Analyzer;

■ Industrial and mining enterprises;

FEATURES

■ Weight:56KG;

■ Material:Epoxy(HCEP);

■ 15KV 17KV 20KV Outdoor;

■ Rated voltages up to 24 kV;

■ Accuracy class: 0.2 0.5 1 3 3P 6P;

■ Rated voltage primary (KV): 20/√3, 20;

■ Good surface creepage distance:860mm;

■ Seconday voltage: (KV) 0.1√3, 0.12, 0.22;

■ Reasonable structure and robust construction;

■ Rated basic insulation levels (BIL) up to 125 kV;

■ Excellent short circuit and thermal withstand capabilities;

■ IEC60044-2, IEC 61869-1,3 & ANSI/IEEE C57.13 Standards;

■ Convenient installation, suitable for installation in any location;

PARAMETERS

Technical parameters
Standards IEC60044-2; IEC 61869-1,3; ANSI/IEEE C57.13; GB20840-1,3
Rated Voltage 24KV, 20KV, 17KV, 15KV
Rated load ≤3000VA
Secondary voltage output 100V, 110V, 120V, 220V, 380V
Rated frequency 50Hz or 60Hz
Cosø 0.8 (lag)
Phase number single phase
Class 0.2, 0.5, 1, 3, 3P, 6P
Windings single, double, three windings
Rated insulation level 24/65/125KV
With fuse Yes, 0.2A
Using type Outdoor
Surface creepage distance 860mm
Application Measurement and Protection
Class of pollution IV
Mechanical parameters
Material Epoxy resin + silicone sleeve
Weight (kg) 56
Operating conditions
Operating temperature -40°C to +60°C
Daily average temp <+40°C
Storage temperature -50°C to +70°C
Altitude <3000 meters
Condition No existence of severely begrimed, erosive and radioactive gas in the air. Permission of long-term operation under rated current.

TECHNICAL DATA

Model Rated Voltage Ratio(KV) Accuracy class and Rated secondary output (VA) Limited output (VA) Rated insulation level (KV) Surface creepage distance (mm) Primary fuse (A) Weight (KG)
JSZW-20 20000/100 0.2---40
0.5---100
1---250
3---500
800 24/65/125 860 0.2 56
20000/220
20000/100/100 0.2/0.2---20/20
0.2/0.5---20/30
0.5/0.5---50/50
400/400
20000/220/220 500/800
JDZXW-20G
20000/√3
100/√3 100/√3
0.2/6P(3P)---30/100
0.5/6P(3P)---60/100
1/6P(3P)---150/100
3/6P(3P)---250/100
600
20000/√3
100/√3 100/√3 100/√3
0.2/0.2/6P(3P)---15/15/100
0.2/0.5/6P(3P)---15/15/100
0.5/0.5/6P(3P)---40/40/100
300/300