>Product>CT & PT>Instrument Voltage Transformer>HV HIGH ALTITUDE 0.2 CLASS 33KV POTENTIAL TRANSFORMER

0.2 potential transformer 33KV
0.2 potential transformer 33KV

GFJDZ0987-35HV HIGH ALTITUDE 0.2 CLASS 33KV POTENTIAL TRANSFORMER

GFJDZ0987-35 35KV HIGH VOLTAGE POTENTIAL TRANSFORMER are designed for metering and protection applications. This product has the characteristics of high efficiency and large capacity, and can be customized according to customer requirements.
The primary and secondary coils are wound using special winding and shielding techniques for improved voltage stress distribution.Each coil is carefully insulated with mylar film to provide a high dielectric medium between layers. The completed winding structure and double-loop cores are assembled to a support frame.

DESCRIPTIONFor insulation and protection, the assembly is cast in hydrophobiccycloaliphatic epoxy (HCEP) using automatic vacuum pressure. The HCEP material offers superior arc track, ozone, and ultraviolet-resistive properties while maintaining physical strength. The hydrophobic surface properties of HCEP ensure highly reliable performance in wet, humid, or polluted environments.
It can be used for 35KV distribution line, Coal mine,power plant,Rail way, factories.. . Strictly Comply IEC60044-2; IEC 61869-1,3; ANSI/IEEE C57.13.

APPLICATION

■ Rail way;

■ Coal Mine;

■ Power Plant;

■ Power Meter;

■ Energy meter;

■ Power station;

■ MV switchgears;

■ Oil, gas company;

■ Distribution boxes;

■ Distribution system;

■ Air insulation cabinet;

■ Ring network cabinet;

■ Measuring instrument;

■ Electric Power Bureau;

■ MV Power Quality Analyzer;

■ Industrial and mining enterprises;

FEATURES

■ Weight:100KG;

■ Using Life: 30 years;

■ Material:Epoxy (HCEP);

■ Rated voltages up to 36kV;

■ High altitude design application;

■ 27KV 33KV 35KV 36KV indoor;

■ Accuracy class: 0.2 0.5 1 3P 6P;

■ Limiting Therminal Output(VA): 400VA/800VA;

■ Reasonable structure and robust construction;

■ Rated basic insulation levels (BIL) up to 200 kV;

■ Rated Voltage Ratio(KV)35/0.1/0.1 or 33/0.1/0.1;

■ Excellent short circuit and thermal withstand capabilities;

■ IEC60044-2, IEC 61869-1,3 & ANSI/IEEE C57.13 Standards;

PARAMETERS

Technical parameters
Standards IEC60044-2; IEC 61869-1,3; ANSI/IEEE C57.13; GB20840-1,3
Rated Voltage 27KV, 33KV, 35KV, 36KV
Rated load ≤30VA or 80VA or 250VA
Secondary voltage output 100V, 110V, 120V, 220V, 380V
Thermal rating burden 800VA
Rated frequency 50Hz or 60Hz
Cosø 0.8 (lag)
Phase number Single
Class 0.2, 0.5, 1, 3, 3P, 6P
Windings single, double
Rated insulation level 40.5/95/200KV
Using type Indoor, double pole
Application Measurement and Protection
Insulation class E
Class of pollution II
Mechanical parameters
Material Epoxy resin
Weight (kg) 100
Operating conditions
Operating temperature -25°C to +55°C
Daily average temp <+40°C
Storage temperature -40°C to +70°C
Relative Air Humidity 15%-85%
Altitude <3000 meters
Condition No existence of severely begrimed, erosive and radioactive gas in the air. Permission of long-term operation under rated current.

TECHNICAL DATA

Model Rated Voltage Ratio(KV) Accuracy Class Combination Rated output (VA) Limiting Therminal Output(VA)
GFJDZ0987-35 35/0.1 0.2
0.5
60
120
800
35/0.1/0.1 0.2/0.2
0.2/0.5
0.5/0.5
20/20
20/30
40/40
400
GFJDZ0987-33 33/0.1 0.2
0.5
60
120
800
33/0.1/0.1 0.2/0.2
0.2/0.5
0.5/0.5
20/20
20/30
40/40
400