>Product>Electrical Test Equipment>Protection Relay Tester>Three Phase Secondary Current Injection Test Set
The Test-330B three phase secondary current injection test set is the first choice for applications requiring very high accuracy more than 0.1%. This unit is not only an excellent test set for protection devices of all kinds but also a universal calibrator. This secondary injection tester can as a ac or dc current source and voltage, and output 2 to 21 times harmonics, max current 90A, max voltage 300V. TEST-330B injection test equipment with PC control software.
Its unique accuracy and reliability make the Test-330B ideal for protection and measurement equipment manufacturers for research and development, production and electric power company type testing.
■ Power plant;
■ Universities;
■ Panel manufacturer;
■ Relay manufacturers;
■ Research institutes;
■ Electrical laboratory;
■ Electrical testing center;
■ Power engineering commissioning company;
■ Electricity power bureau & power company;
■ Electrical Department of industrial and mining enterprises;
■ U/I test ■ DC test ■ I-T test ■ Special test ■ Harmonic test ■ Oscillation test ■ Differential relay ■ State sequence ■ Fault Recurrence ■ Setting group test ■ Hardware checkout ■ Distance protection ■ Metering instrument ■ Power direction test ■ Synchronization test ■ Frequency Protection ■ Differential protection ■ Impedance characteristics ■ Low Voltage protection ■ Zero sequence protection
■ 8 binary input, 4 binary output
■ Intelligent self-protection function
■ High-accuracy linear power amplifier
■ Plentiful Binary and powerful software function
■ Eight-path synchronous D/A output in a single machine
■ 3 phase current output, 5 phase voltage output, Accuracy 0.1%
■ Embedded host machine equipped with Complex Programmable Logic Device (CPLD)
■ Host machine integrated single cabinet structure with big LCD screen and complete interface has obtained appearance patent
■ Synchronous output of five-phase voltage and three-phase current, Max AC current output is 90A, Max AC voltage output is 260V
■ Easily complete the ABB, Siemens, AREVA, Schneider, GE, SEL, VAMP, Toshiba, NR, Sifang and other foreign manufacturers of protective device test
| Electrical parameters | |
|---|---|
| Power voltage | AC220V±10% or AC110V±10%, 50/60Hz±10% |
| AC current output | |
| Phase current output (effective value) | 3 x 0-30A |
| Maximum power output | 260VA/phase |
| Maximum parallel current output (effective value) | 0-90A |
| Long-term allowable working value of phase current (effective value) | 0-10A |
| Rosolution | 1mA |
| Allowable working time of maximum current | >11s |
| Accuracy class | <±0.1% , Typital 0.05% |
| AC voltage output | |
| Phase voltage output (effective value) | 5 x 0-130V |
| Line voltage output (effective value) | 0-260V |
| Maximum power output | 70VA/phase |
| Rosolution | 1mV |
| Accuracy class | <±0.1% , Typital 0.05% |
| Power output | |
| Accuracy class | <±0.1% , Typital 0.05% |
| Frequency output | |
| Output frequency | 0-1050Hz |
| Frequency error | <±0.001Hz |
| Phase angle output | |
| Phase angle | -180.000°-0-180.000°, 0.000°-360.000° |
| Phase error | ><±0.1°, Typital 0.05° |
| DC current output | |
| Output range | -10 to 10A or 3 x 0 to ±10A |
| Maximum power output | 200VA |
| Accuracy class | <±0.1% , Typital 0.05% |
| DC voltage output | |
| Output range | 0-300V or 5 x 0 to ±130V |
| Maximum output power | 130VA |
| Accuracy class | <±0.1% , Typital 0.05% |
| Binary input | |
| Idle contact | 1-20mA, 24V (DC) |
| Electric potential contact | 250V/0.5A (DC) |
| Binary input number | 8PCS |
| Binary output | |
| Idle contact | 250V/0.5A (DC) |
| Binary output number | 4PCS |
| Function | |
| Waveform distortion | <±0.3% (fundamental wave) |
| Time measurement | 0.1ms-999999.999s |
| Time error | <40µs |
| Superposed harmonic wave | 0-21times |
| GPS | Optional |
| LCD | 8 inch color TFT LCD |
| Key | 24pcs key |
| Communication port | RS232, USB, VGA, 10/100M LAN |
| Standard | IEC 61010, IEC 61000, IEC 61326 |
| Mechanical parameters | |
| Dimensions (L×W×H) (mm) | 360x195x375 |
| Weight (kg) | 16.6 |
| Environmental conditions | |
| Operation temperature | 0°C to 50°C |
| Storage temperature | -25°C to 70°C |
| Humidity range | Relative humidity 5 ... 95 %, non-condensing |
| ANSI Standard Device | ||
|---|---|---|
| List of Device Numbers | Relay or Circuit Rreaker | FUNCTION |
| 2 | Time Delay Starting or Closing Relay | Yes |
| 21 | Distance Relay | Yes |
| 24 | Over-Excitation Relay | Yes |
| 25 | Synchronizing or Synchronism-Check Device | Yes |
| 27/27N | Undervoltage Relay | Yes |
| 30 | Annunciator Relay | Yes |
| 32 | Directional Power Relay | Yes |
| 36 | Polarity or Polarizing Voltage Devices | Yes |
| 37 | Undercurrent or Underpower Relay | Yes |
| 40 | Field Relay | Yes |
| 46 | Reverse-phase or Phase-Balance Current Relay | Yes |
| 47 | Phase-Sequence Voltage Relay | Yes |
| 50/50N | Instantaneous Overcurrent or Rate of Rise, Relay | Yes |
| 51/51N | AC Time Overcurrent Relay | Yes |
| 52 | AC Circuit Breaker | Yes |
| 53 | Exciter or DC Generator Relay | Yes |
| 55 | Power Factor Relay | Yes |
| 56 | Field Application Relay | Yes |
| 58 | Rectification Failure Relay | Yes |
| 59/59N | Overvoltage Relay | Yes |
| 60 | Voltage or Current Balance Relay | Yes |
| 61 | Machine Split Phase Current Balance | Yes |
| 62 | Time-Delay Stopping or Opening Relay | Yes |
| 64 | Ground (Earth) Detector Relay | Yes |
| 67/67N | AC Directional Overcurrent Relay | Yes |
| 68 | Blocking Relay | Yes |
| 74 | Alarm Relay | Yes |
| 76 | DC Overcurrent Relay | Yes |
| 78 | Phase-Angle Measuring or Out-of-Step Protective Relay | Yes |
| 79 | AC Reclosing Relay | Yes |
| 81/81U/O/R | Frequency Relay | Yes |
| 82 | DC Reclosing Relay | Yes |
| 85 | Carrier or Pilot-Wire Receiver Relay | Yes |
| 86 | Lockout Relay | Yes |
| 87 | Differential Protective Relay | Yes |
| 91 | Voltage Directional Relay | Yes |
| 92 | Voltage and Power Directional Relay | Yes |
| 94 | Tripping Relay | Yes |