>Product>CT & PT>Instrument Current Transformer> Electrical High Voltage 5p20 Protective Zct Zero Sequence Current Transformer

zero sequence current transformer
zero sequence current transformer
zero sequence current transformer
zero sequence current transformer

LZCG2500-10ELECTRICAL HIGH VOLTAGE 5P20 PROTECTIVE ZCT ZERO SEQUENCE CURRENT TRANSFORMER

The Model LZCG2500-10 ZCT is a ring type resin casting zero sequence current transformer. Some clients also called it as TTCC. This current transformer can be used both for measurement and microcomputer protection of electrical equipment in 11KV and 35KV AC power system such as ABB-Safe Ring/Safe Plus...and cable distribution boxes.
We used imported silicon material and using our mature advanced producing technology we make sure our transformer has very good linear and more than 20 years using life in order to be qualified with all the jobs. The ring core and secondary windings are vacuum poured by high quality epoxide insulated resin ,which has the characteristic of moisture proof, stable performance and dispensing with maintenance. Current transformer protection class 5P20, 5P10, 10P20, 10P10, 10P5.
All of our current transformers are strictly comply IEC60044-1, IEC 61869-2, NTC 2205, GB1208-2006, GB20840.2-2013, ANSI/IEEE C57.13.

APPLICATION

■ Power Meter;

■ Energy meter;

■ MV switchgears;

■ Air switch cabinet;

■ Distribution boxes;

■ Power Quality meter;

■ Ring network cabinet;

■ Measuring instrument;

■ Protective relay device;

■ Current load monitoring;

■ Low voltage metering system;

■ Distribution Power transformer monitor system;

FEATURES

■ Support Dual Ratio;

■ Using life more than 20 years;

■ Measurement range 0-3000A AC;

■ Easily installation, with mounting bracket;

■ High magnetic conductivity silicon steel material;

■ Holding wire diameter: φ120mm, φ140mm, φ160mm;

■ Size:φ120xφ185x100,φ140xφ210x75,φ160xφ250x80;

■ Secondary windings are vacuum poured by insulated resin;

■ High precision 0.2s, 0.2, 0.5s, 0.5, 5P20, 5P10, 10P20, 10P10;

■ IEC60044-1; IEC 61869-2; ANSI C57.13; NTC 2205; GB1208-2006;

PARAMETERS

Technical parameters
Standards IEC60044-1; IEC 61869-2; NTC 2205; ANSI/IEEE C57.13; GB1206-2006;
Rated primary current 50-3000A
Rated load ≤25VA
Rated frequency 50Hz or 60Hz
Rated secondary current 5A or 1A
Rated short-time thermal current 40kA, 1S
Rated continuous thermal current 120%I1n
Secondary winding power-frequency voltage 3kV, 1min
Instrument security factor FS ≤10
Insulation Class E
Material polyurethane +Silicon steel sheets+Enameled wire+ABS
Mechanical parameters
Dimensions (W×D×H) (mm) φ120xφ185x100
Jaw cable diameter(mm) 120, 140, 160
Weight (kg) 7, 8, 9
Operating conditions
Operating temperature -40°C to +70°C
Daily average temp <+40°C
Storage temperature -40°C to +70°C
Altitude <3500 meters
Condition No existence of severely begrimed, erosive and radioactive gas in the air. Permission of long-term operation under rated current.

TECHNICAL DATA

Type LZCG2500-10
Purpose Measuring current transformer Protection current transformer Double winding current transformer
Ratio Accuracy class and rated load(VA) Accuracy class and rated load(VA) Composite Accuracy class and rated load(VA)
I1/I2 0.5 1 3 10P15 10P10 10P5 0.5 1 10P10 10P5
100/1 2 2.5 5 2 2.5 5 2 2.5 1.5 2
200/1 2 2.5 5 3 5 7.5 2.5 2.5 2 2
300/1 2.5 3.75 5 3 5 7.5 3.75 3.75 2.5 2.5
400/1 2.5 5 10 3 5 10 5 5 2.5 2.5
500/1 2.5 5 10 3.75 6.25 10 5 5 2.5 2.5
600/1 5 7.5 10 5 7.5 10 5 5 5 5
750/1 5 7.5 10 5 5 5 5
800/1 5 10 15 5 5 5 5
1000/1 5 10 15 5 5 5 5
1200/1 10 15 20 10 10 10 10 15 2.5 5
1500/1 10 15 20 10 10 10 10 15 2.5 5
1600/1 20 25 30 10 10 10 10 15 2.5 5
2000/1 20 25 30 10 10 10 10 15 2.5 5
50/5 2.5 2
75/5 2.5 2.5
100/5 2.5 2.5 2.5 2.5 2.5 2.5
200/5 2.5 2.5 2.5 5 2.5 5 2.5
300/5 5 5 5 2.5 5 7.5 5 5 2 2.5
400/5 5 5 5 2.5 5 7.5 5 7.5 2.5 5
500/5 5 7.5 10 5 7.5 10 5 7.5 2.5 5
600/5 5 7.5 10 5 7.5 10 5 10 2.5 5
750/5 7.5 10 15 5 10 10 7.5 10 2.5 5
800/5 7.5 10 15 5 10 10 7.5 15 2.5 5
1000/5 10 15 20 10 10 10 10 15 2.5 5
1200/5 10 15 20 10 10 10 10 15 2.5 5
1500/5 10 15 20 10 10 10 10 15 2.5 5
1600/5 20 25 30 10 10 10 10 15 2.5 5
2000/5 20 25 30 10 10 10 10 15 2.5 5
2500/5 20 25 30 10 10 10 10 15 2.5 5
3000/5 20 25 30 10 10 10 10 15 2.5 5

SELECTION GUIDE

Model Primary rated current Rated load Aperture (mm) Description (mm) Weight (kg)
LZCK310-10 300-1000A ≤10VA φ50 φ50 x φ110 x 32 1
LZCK322-10 30-1000A ≤10VA φ50 φ50 x φ110 x 52 1.6
LZCK350-10 30-1000A ≤25VA φ50 φ50 x φ110 x 105 3.1
LZCK720-10 30-1000A ≤25VA φ80 φ80 x φ110 x 50 2.1
LZCK2500-10 30-3000A ≤30VA φ120,140,160 φ120 x φ185 x 100 7
LZCG530-10 30-1000A ≤20VA φ45 φ45 x φ120 x 65 2.1
LZCG930-10 30-1500A ≤25VA φ60 φ60 x φ155 x 60 3.6
LZCT722-10 30-1500A ≤10VA φ82 φ82 x φ130 x 55 2.3
LZCG2500-10 30-3000A ≤30VA φ120,140,160 φ120 x φ185 x 100 7