>Product>Electrical Test Equipment>Power Qulity Analyzer>Three Phase Portable Harmonic Power Quality Analyzer
GF335 three phase harmonic power analyzer with 1000A clamp on ct offer the best ability in power quality analysis, GF335 portable power quality analyzer help locate, predict, prevent and troubleshoot power quality problems in three phase and single phase power distribution systems. Additionally, GFUVE patented energy loss algorithm, unified power measurement, measuring and counting energy losses due to harmonics and unbalance issues, allowing the user to pinpoint the origin of energy losses in the system. GF335 Three Phase Power Analyzer is suitable for Power Company, technical supervision departments, Industrial, mining, petroleum as well as chemicals, home appliances and manufacturing enterprises.
■ Check Meter - real live load calibration of various single-phase, three-phase energy meters.
■ Vector analysis - based on the voltage, current, phase error of judgment wiring, display vector graphics.
■ Measurement of harmonics - measurement / display voltage and current waveforms and harmonic bar graph.
■ Measurement the instantaneous values - including the exchange parameters: U, I, P, Q, PF, phase angle, frequency, harmonics, etc.
■ The value of the measurement process- it can be recorded and tested continuously voltage, current, active power, reactive power and other electrical parameter values and curves in a dynamic process and graphically display.
■ Measuring energy consumption values - the precise timing measurements of electrical equipment for short-term energy consumption; energy resolution: milli-watts; time resolution: milli-second; they are difficult to available for common instrument of power. The functions are used by pumping, cranes, air conditioning and other equipment in a work cycle connected power consumption.
■ The measured data can record, query and upload print.
■ Ultra-compact design, portable, small size, light weight.
■ It can measure harmonic content from 2 to 64 and the harmonic analysis.
■ It can be divided into direct current clamp measurements and precision measurements.
■ Instrument calibration by using software to facilitate the correction instrument variation.
■ Showing the AC waveform, vector diagram and determining the three-phase three-wire connection errors.
■ High accuracy instrument, good stability, and wide range of voltage monitoring 0-1200V, current 1mA - 1000A.
■ The usage of multi-channel power supply, AC power supply can also be rechargeable battery-powered machine.
■ It can measure three-phase voltage , current, active power, reactive power, power factor , frequency, phase , etc.
Items | Range | Resolution | Accuracy1 | Accuracy2 | Remarks |
---|---|---|---|---|---|
Voltage | 0-1200V | 0.001V | 0.1% | 0.05% | 2 ranges |
Current | 0-12A | 0.001A | 0.1% | 0.05% | 3 ranges |
Clamp-on | 0.01-100A | 0.01A | 0.15% | 0.15% | Option(2) |
Clamp-on | 0.1-1000A | 0.1A | 0.2% | 0.20% | |
Frequency | 45-65Hz | 0.001Hz | 0.005Hz | 0.002Hz | 6 bit display |
Active power | 0 to ±Umax x Imax | 0.01W | 0.5% | 0.2% | 6 bit display |
Reactive power | 0 to ±Umax x Imax | 0.01Var | 1% | 0.5% | 6 bit display |
Apparent power | 0 to ±Umax x Imax | 0.01VA | 1% | 0.5% | 6 bit display |
Active energy | 0.5% | 0.2% | |||
Reactive energy | 1% | 0.5% | |||
Harmonic | 2nd-64th | 0.5% | 0.2% | ||
Power factor | 0 to ±0.9999 | 0.0001 | ±0.001 | ±0.0005 | 6 bit display |
Phase | 0-359.999° | 0.005° | ±0.05° | ±0.02° | 6 bit display |
(1) Directly test (2) Clamp-on 1000A,3000A,5000A is optional. |
|||||
Electrical parameters | |||||
Power supply | One-phase power supply (85-265VAC/45-70Hz) Lithium battery, 5000mAh |
||||
Communication port | RS232 | ||||
Energy constant | 3600imp/kWh, 360000imp/kWhx4 | ||||
Frequency Influence | ≤20ppm/Hz | ||||
Pulse Interface | TTL energyx6 | ||||
Mechanical parameters | |||||
Main machine (L×W×H) (mm) | 240×157×60 | ||||
Weight (kg) | 1.5 | ||||
Carrier dimension (L×W×H) (mm) | 470×380×220 | ||||
Carrier weight (kg) | 10.6 (Including three clamp-on (100A), wires and software) | ||||
Environmental conditions | |||||
Environment | -10 to +55°C, 15-85%RHD | ||||
Altitude (m) | ≤3500 | ||||
Temperature | -20°C to 65°C | ||||
Temperature | ≤25ppm/°C (U/I), ≤50ppm/°C (others) |