FUD-U/I Single-phase AC Current Transducer is a high accuracy high load capacity ac current to dc current voltage transducer for industrial power control and monitoring. It accepts 0-1AAC,0-5AAC, 0-10AAC or 0-100V AC, 0-220V AC, 0-380V AC, 0-500V AC input, and converts the input into standard 4-20mA, 0-20mA, 0-5V, 0-10V, 1-5V output. Its input, output, power supply are isolated, 220V AC/DC OR 20-60V DC. It have the linear scale Excellent temperature characteristic and good working stability Configuration compactness and briefness. Many transducer application in industrial system in the field.
■ Oil system;
■ Power plant;
■ Industrial filed;
■ Coal auto system;
■ Rail electrical system;
■ Electricity power company;
■ Metallurgy electrical system;
■ Standard DIN install;
■ Excellent linear transducer;
■ AC input range can be customized;
■ DC output range can be customized;
■ Accuracy class can reach 0.2% or 0.5%;
■ Single phase current / voltage transducer;
■ AC current transducer / voltage transducer;
■ 85-265V AC/DC and 20-60V DC power supply optional;
Technical Index | |
---|---|
Standard | GB/T 13850-1998, IEC688:1992 |
Accuracy | 0.2%, 0.5% |
Consumption | ≤3VA |
Accuracy drift | Annual variation <0.2% |
Insulation voltage | AC 2kV/min.1mA (Between input- output/power) |
Insulation resistance | ≥20MΩ (DC500V) |
Surge voltage | 5KV (Peak value), 1.2/50μs |
Response time | ≤350ms |
Input range | AC 0-10A ,AC 0-500V(Option), 50/60Hz |
Absorbed power | <0.5VA/450V, <0.2VA/100V, <0.1VA/5A |
Overload | Current: 2 times continuous, 30 times/1s; Voltage: 2 times continuous |
Load resistance | Current output: RL ≤550Ω |
Voltage output: RL ≥2kΩ | |
Working environment | Temperature: -10 to +50°C |
RH: 20-90%, without condensation | |
Storage conditions | Temperature: -40 to +70°C |
RH: 20-95%, without condensation | |
Installation | 35mm DIN sliding-way or M4 screws |
Dimension | 55mm x 75mm x 120mm |
FUD-Type-Input-Power Supply-Output | |
---|---|
Type | I: Single phase AC current transducer U: Single phase AC voltage transducer Ir: Single phase AC real RMS current transducer Ur: Single phase AC real RMS voltage transducer |
AC input | A1: 0-1A, A2: 0-5A, A3: 0-10A. V0: 0-70V, V1: 0-120V, V2: 0-250V, V3: 0-300V, V4: 0-450V, V5: 0-500V. |
Power supply | P1: AC 85-265V or DC 100-330V, P2: DC 20-60V. |
DC output | O1: 0-5V, O2: 1-5V, O3: 0-20mA, O4: 4-20mA, O5: RS485. |
Example 1: FUD-I-A2-P2-O4 | |
FUD series single phase AC current transducer | Input: AC0-5A Power supply: AC220V±15% Output: DC4-20mA |
Example 2: FUD-Ur-V3-P2-O4 | |
FUD series single phase AC real RMS voltage transducer | Input: AC 0-300V Power supply: AC220V±15% Output: DC4-20mA |
*Please check the type, input range, output range and power supply when your order the product. |