>Product>Current Probe>AC Current Clamp>Split Core 150mm 3000/5a Current Transformer Clamp
The model Q150 current transformer clamp can be used in large current situation and cooperate to cable fault tester and cable identification device, used for cable test work. It can even measure up to 3000A AC large current and output 0-5A AC current for other measuring or analyzing system. It can provide 0.5% accuracy class result, ratio 1000/5A, 2000/5A or 3000/5A. Suitable for power plants, factoris and mines to measure power load.
■ HVAC;
■ Power meter;
■ Energy meter;
■ Oscilloscopes;
■ Electrical utility;
■ Cable fault tester;
■ Plant maintenance;
■ Electrical Laboratory;
■ Large industrial loads;
■ Power load monitoring;
■ Data logging/recording;
■ Power quality analyzer;
■ Industrial maintenance;
■ Power quality monitoring;
■ Power and harmonic meters;
■ Measuring around cable bundles;
■ Clamp type ground resistance tester;
■ Electric energy meter calibrator on site;
■ UL, CE CNAS mark;
■ Large jaw opening designed;
■ Holding wire diameter: φ150mm;
■ Frequency 40Hz-2000Hz Bandwidth;
■ Conforms to EN 61010, 600V CAT III;
■ Measurement range of 1A to 3600A AC;
■ Low phase shift for power measurement;
■ Precision 0.5% for current measurement;
■ Industrial design & beautiful appearance;
■ Transformation ratio: 1000:5, 2000:5, 3000:5
■ Improved ergonomic design & easy operation;
■ Output:5mA AC/A AC, 2.5mA AC/A AC, 1.666mA AC/A AC;
■ Nominal range: 1 to 1000AAC, 1 to 2000AAC, 1 to 3000A AC;
■ When less than 1A output, load capacity ≤20Ω; When 5A output, load 2.5VA;
■ Designed for cable fault analysis, recorders, loggers, power and harmonic meters;
Electrical parameters | |
---|---|
Ratio | 600: 1 , 1000:1, 2000:1, 3000:1 (customized) |
Accuracy class | 0.2%, 0.5%, 1% |
Primary current | 0 - 3000A AC |
Secondary current | 0 - 5A AC (customized) |
Max. Cont. Input current | 3600A |
Load capacity | ≤2.5VA or 20Ω |
Over voltage category | CAT III 600 V |
Output signal (AC current) | 500mA,1A,5A AC at nominal input current |
Output signal (AC voltage) | 333mV,500mV,1V,5V AC at nominal input current |
Frequency range | 40Hz-2000Hz |
Dielectric strength | 3KV 50Hz/60Hz at 1 minute |
Temperature range | -20°C to +55°C |
Output | 2.5 meter cable with D01 connector |
Max. voltage not insulated conductors | 720 V |
Standard | EN 61010-1, EN 61010-2-032, EN 61010-2-031 IEC60044-1, & IEC61869-2, 600V CAT III |
Installation | Clamp type |
Output mode | Lead output (2.5m) |
Connector | BNC, 4mm banana, signal cable(2 cores),customized |
Mechanical parameters | |
Dimensions (L x W x H) (mm) | 229x364x 44 |
Weight (g) | 1700 |
Holding wire diameter (mm) | φ150 |
Max. jaw opening (mm) | 150 |
Jaw color | White |
Material | PC+ABS, UL94 V0 |
Model | Rate Current | Max Current | Secondary | Coil Ratio | Burden Resistance | Accuracy |
---|---|---|---|---|---|---|
Q150A5-1000 | 1000A | 1200A | 5A | 200:1 | 2.5VA | 0.5% |
Q150A5-2000 | 2000A | 2400A | 5A | 400:1 | 2.5VA | 0.5% |
Q150A5-3000 | 3000A | 3600A | 5A | 600:1 | 2.5VA | 0.5% |
Q150A1-1000 | 1000A | 1200A | 1A | 1000:1 | 2.5VA | 0.5% |
Q150A1-2000 | 2000A | 2400A | 1A | 2000:1 | 2.5VA | 0.5% |
Q150A1-3000 | 3000A | 3600A | 1A | 3000:1 | 2.5VA | 0.5% |
Q150A2-500 | 500A | 600A | 250mA | 2000:1 | customized | 0.5% |
Q150A2-1000 | 1000A | 1200A | 500mA | 2000:1 | customized | 0.5% |
Q150A3-500 | 500A | 600A | 200mA | 2500:1 | customized | 0.5% |
Q150A3-1000 | 1000A | 1200A | 400mA | 2500:1 | customized | 0.5% |
Q150A3-2000 | 2000A | 2400A | 800mA | 2500:1 | customized | 0.5% |
Q150A4-250 | 250A | 300A | 250mA | 1000:1 | customized | 0.5% |
Q150A4-500 | 500A | 600A | 500mA | 1000:1 | customized | 0.5% |
Q150A4-1000 | 1000A | 1200A | 250mA | 4000:1 | customized | 0.5% |
Q150A4-2000 | 2000A | 2400A | 500mA | 4000:1 | customized | 0.5% |
Notes: Can be customized current probe according to user requirements! |