>Product>Electrical Test Equipment>Energy Meter Test Equipment>Onsite Portable Three Phase Electronic Meter Test Set

portable meter test set
portable meter test set
portable meter test set
portable meter test set
portable meter test set
portable meter test set
portable meter test set
portable meter test set
portable meter test set
portable meter test set

GF313V2ONSITE PORTABLE THREE PHASE ELECTRONIC METER TEST SET

GF313V2 onsite portable three phase electronic meter test set is the newest product produced by our company by widely visiting users and referring to the advantages of the same kind of products home and abroad. The measured part of the product adopts high speed A/D transmission to send DSP to conduct digital processing, which largely improves measured degree of accuracy and stability. Central processing part adopts 32-bit ARM embedded technology to make instrument interface novel, function abundant, operation distinct and easy, and performance steady. Class of accuracy: Class 0.1, 0.2 or 0.5, range from 3×120A/3×600V or 3×200A/3×600V, with comfort design, small size and light weight. The model GF313V2 three phase meter meter test set is suit for metrological service of electricity power utilities, industrial and mining enterprises and electric lab to field use.

FEATURES

■ Vector display;

■ Screenshot function;

■ 7 inch color TFT touch LCD;

■ Self adjusted clamp-on CTs;

■ RS232 port for PC software control;

■ Measurement for energy register;

■ USB and RS232 communication ports;

■ Accuracy class: 0.1%, 0.2% or 0.5%;

■ Measurement of clock error of energy meter;

■ Automatic temperature compensation technology;

■ Large capacity storage device for mass memory;

■ Measurement of turn ratio & phase error for CT;

■ Measurement of three phase energy meter errors;

■ Testing comprehensive error of measuring device;

■ 100A, 200A, 500A, 1000A, 2000A, 3000A clamp optional;

■ Measurement of single phase energy meter errors onsite;

■ Power supply (lithium battery)/ 85-265V AC /U1Un (40-450V);

■ Measurement voltage & current of harmonics of 2nd to 63rd;

■ Check wiring failures and calculation of electricity compensation;

■ Testing all kinds of mechanical and electronic energy meter error;

■ Measurement of U, I, P, Q, S, phase angle, power factor, frequency etc;

■ Input two pulse signal for master and slave meter synchronously calibration;

■ With smart optical sampler, suitable for electronic meters and mechanical energy meters;

APPLICATION

■ Power plant;

■ Power engineering company;

■ Metrological service center;

■ Electricity power utilities;

■ Distribution power corporation;

■ Electrical engineering service company;

■ Electricity power bureau & power company;

■ National Metrology and testing department;

■ Electrical Department of industrial and mining enterprises;

PARAMETERS

Electrical parameters
Accuracy class 0.1%, 0.2%, 0.5%
Power Supply External power, 85-265V, 45-65Hz
Phase voltage supply 40-450V, 45-65Hz
Li-Battery supply
Voltage measurement(U1, U2, U3, UN)
Range 0-600V
Error ±0.1%(30-600V); ±0.05%(30-600V)
Harmonic 2nd - 63rd
Input impedance range 245kΩ@ 250V; 10MΩ @5V
Stability 0.01%/minute
Long term stability <100× 10E -6 /Year
Current measurement(Clamp CT - I1, I2, I3)
Range (clamp CT) 0-5A, 0-20A, 0-120A, 0-200A, 0-500A, 0-1000A, 0-2000A, 0-3000A
Clamp on CTs Optional 5A, 20A, 100A, 200A, 500A, 1000A, 2000A, 3000A
Error ±0.1%, ±0.2% , ±0.5%
Harmonic 2nd - 63rd
Clamp diameter 18mm
Input impedance range 0.04Ω@ 0.01A-120A or 0.02-200A
Stability 0.02%/minute
Long term stability <100 × 10E -6 /Year
Power measure error
Active power ±0.1%, ±0.2%, ±0.5%
Reactive power ±0.2%, ±0.5%
Stability 0.02%/minute
Long term stability <100 × 10E -6 /Year
Energy measure error
Active energy ±0.1%, ±0.2%, ±0.5%
Reactive energy ±0.2%, ±0.5%
Stability 0.02%/minute
Long term stability <100 × 10E -6 /Year
Phase angle
Range 0°-360°
Resolution 0.01°
Error ±0.05°
Frequency
Range 40Hz-70Hz
Resolution 0.0005Hz
Error 0.001Hz
Reference Meter
Measuring modes 2WA / 2WR / 2WAP
3WA / 3WR / 3WAP / 3WRCA / 3WRCB
4WA / 4WAb / 4WR / 4WRb / 4WAP / 4WAPb / 4WRC
Brandwidth 3000Hz
Sampling 16 bit 504 samplers / period
Pulse output
Energy constant 25000
Pulse ratio 1:1
Output level 5V
Pulse input
Input channel 2
Input level 3-12V
Input frequency Max. 2M Hz
Display
Resolution 800×480
LCD 7" TFT color touch
Function
Vector diagram Yes
Waveform Yes
Energy Register test Yes
CT ratio test Yes
CT PT programmable Yes
Local parameter input Yes
Wiring emulation Yes
Self-calibration Yes
Recorder check Yes
Data storage Yes
GPS Optional
Data storage qty 10000
External extend memory Yes
Screen printing Yes
Communication port USB/RS232/BT
Communication with PC Yes
Upload data Yes
External mini printer Yes, Optional
External keyboard Yes, 26pcs keys
Safety
IP class according to DIN EN 60529 IP42
Declaration of conformity CE & CNAS conform
Protection class according to DIN EN 61140 II
Overvoltage category voltage measurement CAT III 600V
Overvoltage category current CAT III 600V
Standard
lsolation protection IEC 61010-1:2001
Energy measurement IEC/EN 60736
Reference standard IEC 62052-11
IEC62053-21
IEC62053-22 & IEC62053-23
IEC61010-1:2001
Mechanical parameters
Dimensions (W×H×D) (mm) 245 × 168 × 70
Weight (kg) 1.8
Portable box weight (kg) 7.8
Environmental conditions
Ambient temperature -25°C to +50°C
Storage temperature -30°C to +65°C
Relative humidity 30%-95%
Power Consumstion ≤13VA

PACKING LIST

Item Name QTY
1 GF312V2 machine 1PC
2 P18 100A Clamp on ct(Max 120A) 3PCS
3 Scanning head 1PC
4 Energy pulse cable 1PC
5 Voltage Test cable 1SET
6 RS232 communication cable 1PC
7 Crocodile clip 4PCS
8 Opreration Manual 1PC
9 Factory test certificate 1PC
10 Portable box 1PC
11 PC management software(U disk) 1PC

CURRENT CLAMP(OPTIONAL)

MODEL Q8A2 Q13 P18 P50 P50
Appearance
Range 5A 20A 200A 500A 1000A
MODEL S50 Q125 S120 FQ-RCTA02 FQ-RCTA02
Appearance
Range 1000A 2000A 3000A 3000A 6000A

LOAD (OPTIONAL)

MODEL GF-5A-3P GF-10A-3P
Range 5A Load 10A Load