>Product>CT & PT>Instrument Current Transformer>24kv High Accuracy Medium Voltage Outdoor Current Transformer
This model GFLZFW2-24W3 outdoor dry type current transformer is used in 15kV, 17.5kV, 20kV, 22kV and 24kV power system, for measuring and protection. It has been used in outdoor pole mounted and transmission line. This product has the characteristics of high efficiency and large capacity, and can be customized according to customer requirements.
DESCRIPTIONFor insulation and protection, the assembly is cast in hydrophobic cycloaliphatic epoxy (HCEP) using automatic vacuum pressure. The HCEP material offers superior arc track, ozone, and ultraviolet-resistive properties while maintaining physical strength. Primary and secondary use pure electrolytic copper, both winding and core have high voltage shielding processing. The hydrophobic surface properties of HCEP ensure highly reliable performance in wet, humid, or polluted environments.
It can be used for less than 24KV distribution line, Coal mine,power plant,Rail way, factories.. . The instrument current transformers are strictly in conformity with IEC60044, IEC 61869, ANSI/IEEE C57.13, NBR6855 etc.
■ Rail way;
■ Coal Mine;
■ Power plant;
■ Power Meter;
■ Energy meter;
■ Power station;
■ Oil, gas company;
■ Distribution system;
■ Measuring instrument;
■ Electric Power Bureau;
■ Primary metering cabinets;
■ MV Power Quality Analyzer;
■ Substation metering and relaying;
■ Industrial and mining enterprises;
■ Weight: 62KG;
■ Using life: 30 years;
■ Rated voltages up to 24 kV;
■ 15KV 17.5KV 20KV 24KV Outdoor;
■ Secondary current output 5A or 1A;
■ Reasonable structure and robust construction;
■ Surface creepage distance more than 490mm;
■ Material:Epoxy(HCEP) + outdoor silicone cover;
■ Rated basic insulation levels (BIL) up to 125 kV;
■ Standard & Special High Accuracy metering classes;
■ Accuracy class: 0.2S 0.2, 0.5S, 0.5, 1, 5P20, 5P10, 10P20;
■ Convenient installation, suitable for installation in any location;
■ IEC60044-1, IEC 61869-2, GB/T 20840.1,2 & ANSI/IEEE C57.13 Standards;
Technical parameters | |
---|---|
Standards | IEC60044; IEC 61869; ANSI/IEEE C57.13, GB/T 20840.1,2 |
Accuracy Class | 0.2s, 0.2, 0.5s, 0.5, 1, 10P10, 10P15, 5P20, 5P10 |
Rated Voltage | 24KV, 20KV, 17.5KV, 15KV |
Rated primary current | 5-2000A |
Rated load | ≤40VA |
Rated frequency | 50Hz or 60Hz |
Rated secondary current | 5A or 1A |
Rated short-time thermal current | 60kA, 1S |
Rated dynamic current | 150kA |
Rated insulation level | 24/65/125KV |
Using type | Outdoor |
Application | Measurement and Protection |
Insulation class | E |
FS | ≤10 |
Surface creepage distance (mm) | 490 |
Mechanical parameters | |
Material | Epoxy resin+ silicone sleeve |
Weight (kg) | 62 |
Operating conditions | |
Operating temperature | -25°C to +55°C |
Daily average temp | <+40°C |
Storage temperature | -40°C to +70°C |
Altitude | <3000 meters |
Condition | No existence of severely begrimed, erosive and radioactive gas in the air. Permission of long-term operation under rated current. |
Rated Voltage(KV) | Rated transformation radio | Accuracy class and relative rated output(VA) | Rated short-time thermal current(kA/S) | Rated dynamic current(kA) | |
---|---|---|---|---|---|
class combination | Rated output(VA) | ||||
20 | 100-75/5 | 0.2 0.5 0.2S 0.5S |
10 15 10 15 |
100×I1n | 250×I1n |
100/5 | 10 | 25 | |||
150/5 | 15 | 37.5 | |||
200/5 | 20 | 50 | |||
300-2000/5 | 60 | 150 | |||
10-75/5 | 0.2/5P20 0.5/5P20 0.2S/5P20 0.5S/5P20 |
10/15 15/15 10/15 15/15 |
100×I1n | 250×I1n | |
100/5 | 10 | 25 | |||
150/5 | 15 | 37.5 | |||
200/5 | 20 | 50 | |||
300-2000/5 | 60 | 150 |