>Product>CT & PT>Instrument Current Transformer>33kv Outdoor High Accuracy Post Type Current Transformer
This model GFLZZW1-35Q outdoor post type current transformer is used in 36KV, 35KV, 33KV, 27KV, 25KV power system, for measuring and protection. It has been used in outdoor pole mounted and transmission line. This product has the characteristics of high efficiency and large capacity, and can be customized according to customer requirements.
DESCRIPTIONFor insulation and protection, the assembly is cast in hydrophobic cycloaliphatic epoxy (HCEP) using automatic vacuum pressure. The HCEP material offers superior arc track, ozone, and ultraviolet-resistive properties while maintaining physical strength. Primary and secondary use pure electrolytic copper, both winding and core have high voltage shielding processing. The hydrophobic surface properties of HCEP ensure highly reliable performance in wet, humid, or polluted environments.
It can be used for less than 36KV distribution line, Coal mine,power plant,Rail way, factories.. . The post type instrument current transformers are strictly in conformity with IEC60044, IEC 61869, ANSI/IEEE C57.13, NBR6855 etc.
■ Rail way;
■ Coal Mine;
■ Power plant;
■ Power Meter;
■ Energy meter;
■ Power station;
■ Oil, gas company;
■ Distribution system;
■ Measuring instrument;
■ Electric Power Bureau;
■ Primary metering cabinets;
■ MV Power Quality Analyzer;
■ Industrial and mining enterprises;
■ Substation metering and relaying;
■ Weight: 80KG;
■ Using life: 30 years;
■ Post type outdoor design;
■ Rated voltages up to 36 kV;
■ Secondary current output 5A or 1A;
■ Tin plated copper primary terminals;
■ 36KV, 35KV, 33KV, 27KV, 25KV Outdoor;
■ Reasonable structure and robust construction;
■ Surface creepage distance more than 1300mm;
■ Material:Epoxy(HCEP) + outdoor silicone cover;
■ Rated basic insulation levels (BIL) up to 200 kV;
■ Standard & Special High Accuracy metering classes;
■ Convenient installation, suitable for installation in any location;
■ Accuracy class: 0.2S 0.2, 0.5S, 0.5, 1, 5P20, 5P10, 10P20, 10P15;
■ IEC60044-1, IEC 61869-2, GB/T 20840.1,2 & ANSI/IEEE C57.13 Standards;
Technical parameters | |
---|---|
Standards | IEC60044; IEC 61869; ANSI/IEEE C57.13, GB/T 20840.1,2 |
Accuracy Class | 0.2s, 0.2, 0.5s, 0.5, 1, 10P10, 10P15, 5P20, 5P10 |
Rated Voltage | 36KV, 35KV, 33KV, 27KV, 25KV |
Rated primary current | 20-1500A |
Rated load | ≤30VA |
Rated frequency | 50Hz or 60Hz |
Rated secondary current | 5A or 1A |
Rated short-time thermal current | 80kA, 1S |
Rated dynamic current | 160kA |
Rated insulation level | 40.5/95/200KV |
Using type | Outdoor |
Application | Measurement and Protection |
Insulation class | E |
FS | ≤10 |
Surface creepage distance (mm) | 1300 |
Mechanical parameters | |
Material | Epoxy resin+ silicone sleeve |
Weight (kg) | 80 |
Operating conditions | |
Operating temperature | -25°C to +55°C |
Daily average temp | <+40°C |
Storage temperature | -40°C to +70°C |
Altitude | <3000 meters |
Condition | No existence of severely begrimed, erosive and radioactive gas in the air. Permission of long-term operation under rated current. |
Rated primary current (A) |
Ith/ls (KA r.m.s.) | Idyn (KA peak) | Accuracy class combination | Rated secondary output(VA) | Surface creepage distance (mm) | Weight(KG) | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
1S/2S | 0.2S | 0.5S | 0.2 | 0.5 | 5P10 | 5P15 | 5P20 | |||||
10 |
2 | 5 | 0.2(S)/0.2(S) 0.2(S)/0.5(S) 0.5(S)/0.5(S) 0.2(S)/5P 0.5(S)/5P |
10 |
10 | 15 | 30 | 50 | 30 | 20 | 1300 | 72 |
15 | 2.7 | 6.75 | ||||||||||
20,25 |
4 | 10 | ||||||||||
30 |
6.3 | 15.7 | ||||||||||
40 |
8.1 | 20.2 | ||||||||||
50 |
10.8 | 27 | ||||||||||
75 |
16.2 | 40.5 | ||||||||||
100 |
21.6 | 51.5 | ||||||||||
150 | 37.8 | 94.5 | ||||||||||
200,250 |
||||||||||||
300,400 |
54 | 110 | ||||||||||
500,600 |
68.4 | 136 | ||||||||||
750,800 |
95.5 | 190 | ||||||||||
1000 |
||||||||||||
1200-1500 |
140 | 200 |