>Product>Power Meter>Power Transducer>4-20ma 3p3w Active And Reactive Power Transducer

power transducer
power transducer

FUD-P3/Q34-20MA 3P3W ACTIVE AND REACTIVE POWER TRANSDUCER

GFUVE FUD-P3/Q3 three phase active power & reactive power transducers measure power in 3 Phase 3 Wire in balanced or unbalanced electrical systems and converts it to an industry standard output signal which is directly proportional to the measured input. It support RS485 port. It adopted SCM technique; excellent stability. Delivering the direction of measured power accurately, applicable for active/reactive power measurement in 3P3W. These Transducers provide an output which is load independent and isolated from the input. These Transducers can measure both Import and Export of Power. The output can be connected to Controllers, Data-Loggers, PLC's Analog/Digital Indicators, Recorders for display, analysis or control. They are ideal for SCADA, Energy Management, Telemetering for Remote, Local as well as Central Monitoring System.

APPLICATION

■ Oil system;

■ Power plant;

■ Industrial filed;

■ Coal auto system;

■ Rail electrical system;

■ Electricity power company;

■ Metallurgy electrical system;

FEATURES

■ Excellent linear transducer;

■ Standard DIN install 35mm;

■ 3P3W active power transducer;

■ 3P3W reactive power transducer;

■ Adopted SCM technique; excellent stability;

■ Accuracy class can be reach 0.2% or 0.5%;

■ 220V/5A, 100V/5A, 57.7V/5A, 380V/5A optional;

■ 4-20mA or 4-12-20mA DC signal output optional;

■ 5000 Volts Industry Best Surge Withstand Capability;

■ Applicable for 3P3W active/reactive power measurement;

■ Provides real-time analog signals to SCADA and energy management systems;

Technical Index

Technical Index
Standard GB/T 13850-1998, IEC688:1992
Accuracy 0.2%, 0.5%
Consumption ≤5VA
Accuracy drift Annual variation <0.2%
Insulation voltage AC 2kV/min.1mA (Between input-output/power)
Insulation resistance ≥20MΩ (DC500V)
Surge voltage 5KV (Peak value), 1.2/50μs
Response time ≤350ms
Input range AC 0-5A ,AC 0-500V(Option), 50/60Hz
Absorbed power Per phase voltage: ≤0.5VA/100V
Per phase current: <0.1VA/5A
Overload Current: 2 times continuous, 30 times/1s;
Load resistance Current output: RL ≤650Ω
Voltage output: RL ≥2kΩ
Working environment Temperature: -10 to +50°C
RH: 20-90%, without condensation
Storage conditions Temperature: -40 to +70°C
RH: 20-95%, without condensation
Installation 35mm DIN sliding-way or M4 screws
Dimension 110mm x 75mm x 66.9mm

Model Description

FUD-Type-Input-Power Supply-Output
Type P3: 3P3W active power transducer
Q3: 3P3W reactive power transducer
PQ3: 3P3W active and reactive power transducer
AC input V1: 100V, V2: 0-220V, V3: 270V, V4: 400V
A1: 0-1A, A2: 0-5A.
Power supply P1: AC 85-265V or DC 100-330V, P2: DC 20-60V.
DC output O1: 0-20mA, O2: 0-±20mA, O3: 4-20mA, O4: 4-12-20mA, O5: 0-1V, O6: 0-±1V, O7: 0-5V, O8: 0-±5V, O9: RS485.
Example 1: FUD-P3-V1-A2-P2-O4
FUD series 3P3W active power transducer Input: AC100V, ±5A , ±866W
Power supply: DC 20-60V
Output: 4-12-20mA DC
Example 2: FUD-PQ3-V1-A2-P2-O4
FUD series 3P3W active and reactive power transducer Input: AC100V, ±5A , ±866W(var)
Power supply: DC 20-60V
Output: 4-12-20mA DC
*Please check the type, input range, output range and power supply when your order the product.