>Product>Electrical Test Equipment>Primary Injection Test Equipment> 200A Portable Primary Current Injection Test Kit
TEST-200 200A primary current injection test kit adopts ARM Chip to control its output process and large capacity of toroidal transformers. It is equipped with current meter; it can show primary current value, second current value, the action time and voltage value. Packing is used as aluminum alloy body with PC panel. LCD screen display single-phase protective relay test device of voltage and current output stopwatch; a full isolation, adjustable AC and DC voltage, AC direct current; an adjustable DC voltage and an adjustable AC voltage; output circuit with double overload protection, high output capacity, small size, light weight, high reliability.
Primary Injection Kit Compact Model TEST-200 is designed to operate on single phase 230/240 Volts AC 50/60 Hz. to develop smooth & continuous test current. The test set gives high current output at low cost and with inherent safety at minimum precaution. TEST-200 is mainly applied to Circuit Breaker testing in the power system, contact resistance test and relay test.
■ Switchgear Testing
■ Ground Grid Testing
■ Primary injection tests
■ Circuit Breaker Testing
■ Protective Relay Testing
■ Recloser and Sectionalizers
■ DC Voltage output up to 300V;
■ AC Voltage output up to 250V;
■ Max current output up to 250A;
■ Built-in digital timer resolution 1ms;
■ Thermal and short-circuit protection;
■ Permanent current up to 200 A, 2KVA;
■ Built-in digital ammeter 0.2% accuracy;
■ Small size, light weight, easy to test on-site;
■ Suite for all kinds of overcurrent relay testing;
■ With high precision 0.0000-99999S Stopwatch;
■ Current injection continuous output from 0-50A;
■ Have one channel DC Auxiliary Output from 0 to 220V;
| Electrical parameters | |
|---|---|
| Accuracy | ±0.5% |
| Power Supply (AC) | 220V±10%·2000VA, 50Hz/60Hz or110V±10%·2000VA, 50Hz/60Hz |
| Current Output (AC) | 200A·5V or 100A·10V |
| Capacity | 2KVA |
| The current output waveform distortion | ≤5% |
| Dual protection | overload electronic protection and software protection |
| Primary current | |
| Range | 0-250A |
| Resolution | 0.1A |
| Accuracy | <0.5% RG |
| AC Voltage Output | |
| Range | 0-250V AC |
| Resolution | 0.1V |
| Accuracy | <0.2% RG |
| DC Voltage Output | |
| range | 0-300V DC |
| Resolution | 0.1V |
| Accuracy | <0.5% RG |
| Current Output duration | |
| 200A range | 200A 1-2minutes 100A 3-6minutes 50A Continuous |
| 10A range | 10A Continuous |
| Stopwatch | |
| Range | 0.0000-99999S |
| Resolution | 0.1mS |
| Accuracy | ±5 words |
| Max input voltage (With contact and potential input) |
DC 250V |
| Ammeter | |
| Range | Inside 0.000-250.0A Outside 0.000-6.000A(AC or DC) |
| Accuracy | <0.2% |
| Voltmeter | |
| Range | 0.0-600.0V(AC or DC) |
| Accuracy | <0.2% |
| Measuring mode | AC True RMS DC Average value |
| Auxiliary Contacts | |
| Binary input/output | one, AC250V*1A or DC120V*1A |
| DC Auxiliary Output | |
| Range | 0-110V DC, max 0.5A; 110-220V DC, max 0.5A |
| Interface | |
| Serial interface | RS232 |
| LCD | 320*240 Greenlight LCD display |
| Resistor | |
| Resistance | 0.5Ω-2.5kΩ |
| Capacitor | 10 μF, max voltage 450 V AC |
| Standard | |
| Standard | 2006/95/EC, EMC 2004/108/EC, IEC61000, IEC61010, IEC 61326 |
| Mechanical parameters | |
| Dimensions (W×D×H) (mm) | 340×270×250 |
| Weight(kg) | 22.5 |
| Environmental conditions | |
| Operating Temperature | -10°C to 50°C |
| Storage temperature | -40°C to 70°C |
| Humidity range | Relative humidity 5 ... 95 %, non-condensing |
| Model | Accuracy | Primary Current | Ammeter(0-6A) | Timer | Power | Injection Current time | Dimension(W×D×H) (mm) | Weight | Remark |
|---|---|---|---|---|---|---|---|---|---|
| TEST-200 | 0.50% | 0-200A | YES | YES | 2KVA | 200A: 2-3min; 100A:3-6min |
340×270×250 | 22.5KG | Integrated structure |
| TEST-901 | 0.50% | 0-1100A | YES | YES | 5KVA | 1000A: 2-3min; 500A:3-6min |
430×260×260 | 25KG | Integrated structure |
| TEST-902 | 0.50% | 0-2200A | YES | YES | 12KVA | 2000A:2-3min; 1000A:3-6min |
360×300×295 and 320×300×300 | 35KG+15KG | Fission structure |
| TEST-903 | 0.50% | 0-3300A | YES | YES | 15KVA | 3000A: 2-3min; 1500A:3-6min |
380×350×360 and 340×290×420 | 48KG+42KG | Fission structure |
| TEST-905 | 0.50% | 0-5500A | YES | YES | 30KVA | 5000A:2-3min; 2500A:3-6min |
430×430×445 and 550×450×600 | 68KG+55KG | Fission structure |